Metering protection
Armored pole-mounted box: protected individual metering
Shields pole-mounted metering against vandalism and the weather, with Bluetooth opening and a mechanical contingency key.

What it is for
Protect metering where it is exposed
3 mm steel sheet, hidden anti-vandalism hinges and a mechanical lock rated for 5 tons.
Open only for whoever should
Bluetooth access control and locking, with individual access and a record of every event. The coded mechanical key remains as a contingency.
Maintain without removing anything
The meter tray slides outward on a runner. The cabinet has ladder supports, lifting handles and an A4 sheet holder.
Seismic alarm on forced opening, with optional automatic cut-off. The box includes a main breaker and busbar, pre-drilled cable entries and PG 16 and PG 48 cable glands.


Technical specifications
Dimensions and structure
- Width
- 1,080 mm
- Total height
- 1,388 mm
- Body height
- 1,260 mm
- Total depth
- 572 mm
- Body depth
- 506 mm
- Material
- 3 mm galvanized carbon steel sheet
- Paint
- Munsell N6.5, 80 µm coat
- Identification
- Stainless steel plate for QR code
Security
- Access
- Bluetooth access control and locking
- Contingency
- Coded mechanical key
- Hinges
- Hidden, anti-vandalism
- Lock
- Mechanical, rated for 5 tons
- Cylinder
- Brass cam cylinder, with telescopic stainless steel pins and hardened-steel anti-drilling pins
- Seismic alarm
- On forced opening, with optional automatic cut-off
Installation and maintenance
- Meter tray
- Sliding runner system
- Mounting
- Pole mounting system
- Ladder and lifting
- Internal and external ladder support; lifting handles
- Cables
- Pre-drilled cable entries; PG 16 and PG 48 cable glands
- Documentation
- A4 sheet holder
- Electrical protection
- Main breaker and busbar
Tests and standards
- ABNT NBR IEC 60529
- Verification of the degree of protection (IP43 code).
- ABNT NBR IEC 62262
- Verification of the degree of protection against external mechanical impacts (IK10 code).
- ABNT NBR 15820
- Electric energy meter box. Mechanical strength test, cover displacement test, verification of axial loads on the metal inserts and verification of corrosion resistance.
Specifications subject to change without notice. Final configurations are defined per project.
Access and installation
Bluetooth opening
Opening is ordered from the operator's phone, with individual access control and a record of every event. The coded mechanical key remains as a contingency.
Electrical interlock, optional
On a forced-opening attempt, the seismic system trips the breaker coil and cuts the power automatically. It is an optional function.
Anti-theft screw and single-line diagram
High-hardness steel key with a secret geometry that does not allow conventional tools; the secret can be regionalized per utility. The installation's single-line diagram is delivered according to the project.